Maximum current allowed in PVC insulated cables with voltage 0.6-1 kV
Wednesday, 15 May 2019
by رسا خطوط
Nominal cross section (mm)² Copper conductors installed in air at 30°C Copper conductors installed in air at 15°C Single strands Double strands (A) 3or4 strands (A) Single strands Double strands (A) 3or4 strands (A) Trianqular (A) Flat (A) Trianqular (A) Flat (A) 16 – – 94 80 – – 117 100 25 – – 119
- Published in news & articels
Low pressure coated air conductors
Wednesday, 15 May 2019
by رسا خطوط
Size of conductor (mm)² Construction Cover thickness (mm) Finished diameter of conductor (mm) App.conductor weight (kg/km) Electrical resistance at 20°C (Ω/Km) Tensile strength (N) Packing (M) 25 7×2.10 1.20 8.70 97 1.181 4200 4000 35 7×2.50 1.20 9.90 130 0.833 5700 4000 50 19×1.80 1.50 12.00 185 0.595 8400 2000 70 19×2.10 1.50 13.50 241
- Published in Low coated wires, Products
Medium pressure coated air conductors
Wednesday, 15 May 2019
by رسا خطوط
Size of conductor (mm)² Construction Cover thickness (mm) Finished diameter of conductor (mm) App.conductor weight (kg/km) Electrical resistance at 20°C (Ω/Km) Tensile strength (N) Packing (M) Al (Nxmm) St (Nxmm) Weasel/35 6×2.59 1×2.59 2.3 11.75 192.8 0.9077 11400 4000 Fox 6×2.79 1×2.79 2.3 12.31 217.7 0.7827 13200 4000 Mink/70 6×2.66 1×3.66 2.3 14.7 340.1 0.4541
- Published in Medium coated wires, Products
Specifications of single-stranded power cables with PVC insulation and coating with 0.6-1 kV voltage
Wednesday, 15 May 2019
by رسا خطوط
Size of cable (mm)² Construction (No-mm) Insulation thickness (mm) Cover thickness (mm) App.diameter of cable (mm) Max electrical resistance at 20°C (Ω/Km) Min insulation resistance at 70°C (MΩ/Km) App.cable weight (kg/km) Packing (m) 1×4 1×2.25 1.0 1.4 7.1 4.61 0.01 84.3 1000 1×4 7×0.85 1.0 1.4 7.4 4.61 0.009 88.5 1000 1×6 1×2.76 1.0
- Published in Products, single core power cable
Characteristics of single-stranded power cables with XLPE insulation and PVC cladding at 0.6-1 kV
Wednesday, 15 May 2019
by رسا خطوط
Size of cable (mm)² Construction (No-mm) Insulation thickness (mm) Cover thickness (mm) App.diameter of cable (mm) Max electrical resistance at 20°C (Ω/Km) Min insulation resistance at 70°C (MΩ/Km) App.cable weight (kg/km) Packing (m) 1×4 1×2.25 0.7 1.4 7.1 4.61 0.768 72 1000 1×4 1×2.25 0.7 1.4 7.4 4.61 0.696 76 1000 1×6 1×2.76 0.7
- Published in Products, single core power cable
Specifications of single-stranded power cables with aluminum conductor, insulation and PVC coating with 0.6-1 kV voltage
Saturday, 11 May 2019
by رسا خطوط
Size of cable (mm)² Construction (No-mm) Insulation thickness (mm) Cover thickness (mm) App.diameter of cable (mm) Max electrical resistance at 20°C (Ω/Km) Min insulation resistance at 70°C (MΩ/Km) App.cable weight (kg/km) Packing (m) 1×16 7×1.70 1.0 1.4 9.9 1.91 0.0053 128 1000 1×25 7×2.12 1.2 1.4 11.6 1.20 0.0051 180 1000 1×35 7×2.50 1.2
- Published in Products, single core power cable
Characteristics of single-stranded power cables with aluminum conductor, XLPE insulation and PVC cladding at 0.6-1 kV
Saturday, 11 May 2019
by رسا خطوط
Size of cable (mm)² Construction (No-mm) Insulation thickness (mm) Cover thickness (mm) App.diameter of cable (mm) Max electrical resistance at 20°C (Ω/Km) Min insulation resistance at 70°C (MΩ/Km) App.cable weight (kg/km) Packing (m) 1×16 7×1.70 1.0 1.4 9.9 1.91 0.386 106 1000 1×25 7×2.12 1.0 1.4 11.6 1.20 0.393 149 1000 1×35 7×2.50 1.2 1.4
- Published in Products, single core power cable
Specifications of flexible cables with PVC insulation and coating with voltage of 300-500 volts
Saturday, 11 May 2019
by رسا خطوط
Size of cable (mm)² Construction (No-mm) Insulation thickness (mm) Cover thickness (mm) App.diameter of cable (mm) Max electrical resistance at 20°C (Ω/Km) Min insulation resistance at 70°C (MΩ/Km) App.cable weight (kg/km) Packing (m) 2×0.75 24×0.2 0.6 0.8 6.3 26 0.0115 55.3 1000 2×1.0 32×0.2 0.6 0.8 6.6 19.5 0.010 63.4 1000 2×1.5 30×0.25 0.7 0.8
- Published in flexible cable, Products
Characteristics of flexible cables with PVC insulation and coating 0.6-1 kV
Saturday, 11 May 2019
by رسا خطوط
Size of cable (mm)² Construction (No-mm) Insulation thickness (mm) Cover thickness (mm) App.diameter of cable (mm) Max electrical resistance at 20°C (Ω/Km) Min insulation resistance at 70°C (MΩ/Km) App.cable weight (kg/km) Packing (m) 2×4 56×0.30 1.0 1.8 12.6 4.95 0.0076 229 1000 2×6 84×0.30 1.0 1.8 13.8 3.30 0.0065 290 1000 2×10 80×0.40 1.0 1.8
- Published in flexible cable, Products
Semiconductor wires with PVC insulation with voltage of 450-750 volts
Saturday, 11 May 2019
by رسا خطوط
Cross section (mm)² Conductor Construction (No-mm) Insulation thickness (mm) Diameter (mm) Max electrical resistance at 20°C (Ω/Km) Min insulation resistance at 70°C (MΩ/Km) App.cable weight (kg/km) Packing (m) 1.5 7×0.53 0.7 3 12.1 0.010 21.5 100 2.5 7×0.67 0.8 3.6 7.41 0.009 32.9 100 4 7×0.85 0.8 4.2 4.61 0.0077 49.1 100 6 7×1.04 0.8